APC Smart-UPS On-Line - SRT3000RMXLI-NC
This 3000VA/2700W On-line pure sine wave UPS provides scalable runtime while minimizing maintenance. The 2U rackmount SRT has a preinstalled Network Management Card in the Smart Slot for UPS network-based monitoring and management.
Product code | 270.172882 |
---|---|
Part number | SRT3000RMXLI-NC |
EAN | 731304327592 |
Manufacturer | APC |
Availability |
In stock 0 pc
Stock allocation and delivery options
Transport company across Europe Thursday 5. 12. at the latest Wednesday 11. 12. |
Supplier availability | In stock 22 pc |
Warranty | 24 months |
Weight | 31.3 kg |
The price includes all legal fees |
Detailed information
-
- Input
Network frequency 40 - 70 Hz auto-sensing Plug standard BS1363A British
IEC 60320 C20
Schuko CEE 7 / EU1-16PInput voltage 230 V Other Input voltage 220 V
240 VInput voltage limits 100 - 275 V adjustable (half load)
160 - 275 V- Output
Rated power in W 2700 W Maximum configurable power in W 2700 W Output frequency 50/60 Hz +/- 3 Hz sync to mains UPS type Double conversion online Waveform type Sine wave Number of power socket outlets 8 IEC 60320 C13
2 IEC Jumpers
2 IEC 60320 C19Output voltage 230 V Other Output voltage 220 V
240 VHarmonic distortion Less than 2 % Crest factor 3 : 1 Bypass type Internal bypass (automatic and manual) - Battery & Runtime
Battery type Lead-acid battery Number of battery filled slots 1 Battery recharge time 3 h Number of battery replacement quantity 1 Additional information Configurable for 220 : 230 or 240 nominal output voltage Liquid value 0 Battery voltage 96 V
-
- Surge Protection & Filtering
Surge energy rate 310 Joules - Physical Characteristics
Dimensions (HxWxD) 85 x 432 x 635 mm Net Weight 31.3 kg Shipping (HxWxD) 246 x 599 x 871 mm Shipping Weight 39.92 kg Color Black - Operating Environment
Ambient air temperature for operation 0 - 40 °C Operating altitude 0 - 10000 ft Relative humidity 0 - 95 % non-condensing Ambient air temperature for storage -15 - 45 °C Storage altitude 0 - 15240 m Acoustic level 55 dBA Heat dissipation 703 Btu/h IP degree of protection IP20 - Conformance
Product certifications CE
EAC
RCM
VDEStandards EN/IEC 62040-1
EN/IEC 62040-2Marking CE Mark - Communications & Management
Free slots 0 Preinstalled device Network management card 2 with environmental monitoring Control panel Multifunction LCD status and control console Alarm Audible and visible alarms prioritized by severity Emergency power off Yes